{"id":82,"date":"2024-12-10T05:30:17","date_gmt":"2024-12-10T05:30:17","guid":{"rendered":"https:\/\/libraryresources.nse.org.ng\/fundamentalsoffoundationengineering\/chapter\/1-9-the-vane-shear-test\/"},"modified":"2026-03-16T13:53:03","modified_gmt":"2026-03-16T13:53:03","slug":"1-9-the-vane-shear-test","status":"publish","type":"chapter","link":"https:\/\/libraryresources.nse.org.ng\/fundamentalsoffoundationengineering\/chapter\/1-9-the-vane-shear-test\/","title":{"raw":"1.9 The Vane Shear test","rendered":"1.9 The Vane Shear test"},"content":{"raw":"The <em>vane shear <\/em>test is performed to measure <em>in situ <\/em>the undrained shear strength <em>S<sub>u<\/sub><\/em> of soft-to-medium clays with undrained shear strength less than 50 kPa.\n\nThe standard procedure for field vane shear tests is described in AS 1289.6.2.1 (<a href=\"https:\/\/oercollective.caul.edu.au\/app\/uploads\/sites\/143\/2024\/12\/1.35-replace-e1747983149601.png\">Figure 1.35<\/a>): A four-blade vane is pushed into the soil, at a depth no closer than four borehole diameters from the immediately above test location, and it is rotated until the soil shears to failure, while measuring the maximum torque <em>T<\/em> necessary to rotate the vane. The standard dimensions of the vane are 130 mm height (<em>H<\/em>) x 65 mm diameter (<em>D<\/em>) x 3 mm thickness (<em>t<\/em>). Both the peak shear strength and the remolded shear strength are measured: the former during the rotation of the vane for 1 minute at a constant rate of 6 deg\/min, and the latter from the constant torque measured after 8-10 additional rapid revolutions. The sensitivity <em>S<sub>t<\/sub><\/em> of the clay is also estimated, as the ratio of the undisturbed peak undrained shear strength to the remolded undrained shear strength (see Section 1.8.3).\n\nThe undrained shear strength is estimated from the measurements obtained during the vane test as:\n\n<strong>(1.34)<\/strong> [latex]{S_u}\\left( {{\\rm{kPa}}} \\right) = \\dfrac{{272.83 \\times {{10}^6}T\\left( {{\\rm{kNm}}} \\right)}}{{{D^3}\\left( {{\\rm{mm}}} \\right)}}[\/latex]\n\nThe above Eq. 1.34 is valid for standard vanes, where <em>H = 2D <\/em>(<a href=\"https:\/\/oercollective.caul.edu.au\/app\/uploads\/sites\/143\/2024\/12\/1.36-replace-e1747983193947.png\">Figure 1.36<\/a>). Note that the skin friction of the vane rod should be accounted for in the calculation of the maximum torque, <em>T<\/em>.\n\n[caption id=\"attachment_79\" align=\"aligncenter\" width=\"1000\"]<img class=\"size-full wp-image-79\" src=\"https:\/\/libraryresources.nse.org.ng\/wp-content\/uploads\/sites\/9\/2024\/12\/1.35-replace-e1747983149601.png\" alt=\"Stages of a vane shear test: The four-blade vane is connected to vane rods and is pushed into soil, 4 diameters lower than the elevation of the previous test. Next, the vane is rotated within 1 min at 6 deg\/min and the peak torque is measured. Afterward, 8-10 quick revolutions of the vane are performed. Finally, the vane is rotated again to measure the residual torque corresponding to the remolded strength.\" width=\"1000\" height=\"623\"> Figure 1.35. Vane shear test procedure (FHWA 2006, U.S. Govt copyright).[\/caption]\n\n[caption id=\"attachment_79\" align=\"aligncenter\" width=\"200\"]<a href=\"https:\/\/oercollective.caul.edu.au\/app\/uploads\/sites\/143\/2024\/12\/1.36-replace-e1747983193947.png\"><img class=\"wp-image-80 size-full\" src=\"https:\/\/libraryresources.nse.org.ng\/wp-content\/uploads\/sites\/9\/2026\/03\/1.36-replace-e1747983193947.png\" alt=\"Schematic of a vane blade with H=2D, with different components indicated.\" width=\"200\" height=\"448\"><\/a> Figure 1.36. Vane and rod mounting[\/caption]\n\nBased on experience from failures of embankments on soft clay immediately after construction, it is acknowledged that the shear vane test tends to overestimate the undrained shear strength. This is due to the fact that clays exhibit viscous behaviour, which suggests that their strength depends on the rate of shearing: the higher the rate, the higher the strength. Therefore a reduction factor <em>\u03bb<\/em><em><sub>v<\/sub><\/em> needs to be considered when estimating the design undrained shear strength (corresponding to time to failure of the order of days\/weeks) from vane tests where failure takes place within 1-2 mins:\n\n<strong>(1.35)<\/strong><em> [latex]{S_{u,design}} = {\\lambda _v} \\times {S_{u,vane}} [\/latex]<\/em>\n\nThis reduction factor depends on the plasticity index PI of the clay (<a href=\"https:\/\/oercollective.caul.edu.au\/app\/uploads\/sites\/143\/2024\/12\/1.37-replace-e1747983235343.png\">Figure 1.37<\/a>), as the higher the plasticity index (increased clay content), the more prominent viscous effects are.\n\n[caption id=\"attachment_79\" align=\"aligncenter\" width=\"1100\"]<a href=\"https:\/\/oercollective.caul.edu.au\/app\/uploads\/sites\/143\/2024\/12\/1.37-replace-e1747983235343.png\"><img class=\"wp-image-81 size-full\" src=\"https:\/\/libraryresources.nse.org.ng\/wp-content\/uploads\/sites\/9\/2026\/03\/1.37-replace-e1747983235343.png\" alt=\"The figure on the left shows the variation of the correction factor \u03bbv with the plasticity index. Results for different soils are fitted with a line, which provides the correction factor for embankment stability analysis. The figure on the left shows again the variation of the correction factor \u03bbv with the plasticity index, but this time different lines are provided, each one corresponding to different time to failure (ranging from 10mins to 10^4 mins).\" width=\"1100\" height=\"460\"><\/a> Figure 1.37. (a) Reduction factor of undrained shear strength obtained from vane shear tests for embankment stability analyses (after Bjerrum 1972); (b) Reduction factor curves as function of the time to failure and of the plasticity index (after Chandler 1988).[\/caption]\n\nThe advantage of the vane shear over other <em>in situ<\/em> testing methods for determining the undrained shear strength (CPTu, Eq. 1.16) is that the interpretation of the former is generally not sensitive to uncertainties regarding the shape of the failure surface (or value of the cone factor <em>N<sub>kt<\/sub><\/em>). It is widely accepted that rotation of a four-blade vane into soft soil will result in a cylindrical failure surface, and this is reflected in Eq. 1.34. Therefore, it is quite common to use vane shear tests to obtain site-specific cone factor values, in other words to calibrate the interpretation of cone test results on vane shear tests. Finally, it must be noted that the undrained shear strength measured by means of vane shear tests is the undrained strength under simple shear conditions (see Kouretzis <em>et al.<\/em> 2017), which in not equal to the undrained shear strength measured during common triaxial compression tests, as the stress path to failure is different. The implications of this when it comes to stability calculations are discussed in Part 5.","rendered":"<p>The <em>vane shear <\/em>test is performed to measure <em>in situ <\/em>the undrained shear strength <em>S<sub>u<\/sub><\/em> of soft-to-medium clays with undrained shear strength less than 50 kPa.<\/p>\n<p>The standard procedure for field vane shear tests is described in AS 1289.6.2.1 (<a href=\"https:\/\/oercollective.caul.edu.au\/app\/uploads\/sites\/143\/2024\/12\/1.35-replace-e1747983149601.png\">Figure 1.35<\/a>): A four-blade vane is pushed into the soil, at a depth no closer than four borehole diameters from the immediately above test location, and it is rotated until the soil shears to failure, while measuring the maximum torque <em>T<\/em> necessary to rotate the vane. The standard dimensions of the vane are 130 mm height (<em>H<\/em>) x 65 mm diameter (<em>D<\/em>) x 3 mm thickness (<em>t<\/em>). Both the peak shear strength and the remolded shear strength are measured: the former during the rotation of the vane for 1 minute at a constant rate of 6 deg\/min, and the latter from the constant torque measured after 8-10 additional rapid revolutions. The sensitivity <em>S<sub>t<\/sub><\/em> of the clay is also estimated, as the ratio of the undisturbed peak undrained shear strength to the remolded undrained shear strength (see Section 1.8.3).<\/p>\n<p>The undrained shear strength is estimated from the measurements obtained during the vane test as:<\/p>\n<p><strong>(1.34)<\/strong> [latex]{S_u}\\left( {{\\rm{kPa}}} \\right) = \\dfrac{{272.83 \\times {{10}^6}T\\left( {{\\rm{kNm}}} \\right)}}{{{D^3}\\left( {{\\rm{mm}}} \\right)}}[\/latex]<\/p>\n<p>The above Eq. 1.34 is valid for standard vanes, where <em>H = 2D <\/em>(<a href=\"https:\/\/oercollective.caul.edu.au\/app\/uploads\/sites\/143\/2024\/12\/1.36-replace-e1747983193947.png\">Figure 1.36<\/a>). Note that the skin friction of the vane rod should be accounted for in the calculation of the maximum torque, <em>T<\/em>.<\/p>\n<figure id=\"attachment_79\" aria-describedby=\"caption-attachment-79\" style=\"width: 1000px\" class=\"wp-caption aligncenter\"><img decoding=\"async\" class=\"size-full wp-image-79\" src=\"https:\/\/libraryresources.nse.org.ng\/wp-content\/uploads\/sites\/9\/2024\/12\/1.35-replace-e1747983149601.png\" alt=\"Stages of a vane shear test: The four-blade vane is connected to vane rods and is pushed into soil, 4 diameters lower than the elevation of the previous test. Next, the vane is rotated within 1 min at 6 deg\/min and the peak torque is measured. Afterward, 8-10 quick revolutions of the vane are performed. Finally, the vane is rotated again to measure the residual torque corresponding to the remolded strength.\" width=\"1000\" height=\"623\" srcset=\"https:\/\/libraryresources.nse.org.ng\/fundamentalsoffoundationengineering\/wp-content\/uploads\/sites\/9\/2024\/12\/1.35-replace-e1747983149601.png 1000w, https:\/\/libraryresources.nse.org.ng\/fundamentalsoffoundationengineering\/wp-content\/uploads\/sites\/9\/2024\/12\/1.35-replace-e1747983149601-300x187.png 300w, https:\/\/libraryresources.nse.org.ng\/fundamentalsoffoundationengineering\/wp-content\/uploads\/sites\/9\/2024\/12\/1.35-replace-e1747983149601-768x478.png 768w, https:\/\/libraryresources.nse.org.ng\/fundamentalsoffoundationengineering\/wp-content\/uploads\/sites\/9\/2024\/12\/1.35-replace-e1747983149601-65x40.png 65w, https:\/\/libraryresources.nse.org.ng\/fundamentalsoffoundationengineering\/wp-content\/uploads\/sites\/9\/2024\/12\/1.35-replace-e1747983149601-225x140.png 225w, https:\/\/libraryresources.nse.org.ng\/fundamentalsoffoundationengineering\/wp-content\/uploads\/sites\/9\/2024\/12\/1.35-replace-e1747983149601-350x218.png 350w\" sizes=\"(max-width: 1000px) 100vw, 1000px\" \/><figcaption id=\"caption-attachment-79\" class=\"wp-caption-text\">Figure 1.35. Vane shear test procedure (FHWA 2006, U.S. Govt copyright).<\/figcaption><\/figure>\n<figure id=\"attachment_79\" aria-describedby=\"caption-attachment-79\" style=\"width: 200px\" class=\"wp-caption aligncenter\"><a href=\"https:\/\/oercollective.caul.edu.au\/app\/uploads\/sites\/143\/2024\/12\/1.36-replace-e1747983193947.png\"><img decoding=\"async\" class=\"wp-image-80 size-full\" src=\"https:\/\/libraryresources.nse.org.ng\/wp-content\/uploads\/sites\/9\/2026\/03\/1.36-replace-e1747983193947.png\" alt=\"Schematic of a vane blade with H=2D, with different components indicated.\" width=\"200\" height=\"448\" srcset=\"https:\/\/libraryresources.nse.org.ng\/fundamentalsoffoundationengineering\/wp-content\/uploads\/sites\/9\/2026\/03\/1.36-replace-e1747983193947.png 200w, https:\/\/libraryresources.nse.org.ng\/fundamentalsoffoundationengineering\/wp-content\/uploads\/sites\/9\/2026\/03\/1.36-replace-e1747983193947-134x300.png 134w, https:\/\/libraryresources.nse.org.ng\/fundamentalsoffoundationengineering\/wp-content\/uploads\/sites\/9\/2026\/03\/1.36-replace-e1747983193947-65x146.png 65w\" sizes=\"(max-width: 200px) 100vw, 200px\" \/><\/a><figcaption id=\"caption-attachment-79\" class=\"wp-caption-text\">Figure 1.36. Vane and rod mounting<\/figcaption><\/figure>\n<p>Based on experience from failures of embankments on soft clay immediately after construction, it is acknowledged that the shear vane test tends to overestimate the undrained shear strength. This is due to the fact that clays exhibit viscous behaviour, which suggests that their strength depends on the rate of shearing: the higher the rate, the higher the strength. Therefore a reduction factor <em>\u03bb<\/em><em><sub>v<\/sub><\/em> needs to be considered when estimating the design undrained shear strength (corresponding to time to failure of the order of days\/weeks) from vane tests where failure takes place within 1-2 mins:<\/p>\n<p><strong>(1.35)<\/strong><em> [latex]{S_{u,design}} = {\\lambda _v} \\times {S_{u,vane}}[\/latex]<\/em><\/p>\n<p>This reduction factor depends on the plasticity index PI of the clay (<a href=\"https:\/\/oercollective.caul.edu.au\/app\/uploads\/sites\/143\/2024\/12\/1.37-replace-e1747983235343.png\">Figure 1.37<\/a>), as the higher the plasticity index (increased clay content), the more prominent viscous effects are.<\/p>\n<figure id=\"attachment_79\" aria-describedby=\"caption-attachment-79\" style=\"width: 1100px\" class=\"wp-caption aligncenter\"><a href=\"https:\/\/oercollective.caul.edu.au\/app\/uploads\/sites\/143\/2024\/12\/1.37-replace-e1747983235343.png\"><img decoding=\"async\" class=\"wp-image-81 size-full\" src=\"https:\/\/libraryresources.nse.org.ng\/wp-content\/uploads\/sites\/9\/2026\/03\/1.37-replace-e1747983235343.png\" alt=\"The figure on the left shows the variation of the correction factor \u03bbv with the plasticity index. Results for different soils are fitted with a line, which provides the correction factor for embankment stability analysis. The figure on the left shows again the variation of the correction factor \u03bbv with the plasticity index, but this time different lines are provided, each one corresponding to different time to failure (ranging from 10mins to 10^4 mins).\" width=\"1100\" height=\"460\" srcset=\"https:\/\/libraryresources.nse.org.ng\/fundamentalsoffoundationengineering\/wp-content\/uploads\/sites\/9\/2026\/03\/1.37-replace-e1747983235343.png 1100w, https:\/\/libraryresources.nse.org.ng\/fundamentalsoffoundationengineering\/wp-content\/uploads\/sites\/9\/2026\/03\/1.37-replace-e1747983235343-300x125.png 300w, https:\/\/libraryresources.nse.org.ng\/fundamentalsoffoundationengineering\/wp-content\/uploads\/sites\/9\/2026\/03\/1.37-replace-e1747983235343-1024x428.png 1024w, https:\/\/libraryresources.nse.org.ng\/fundamentalsoffoundationengineering\/wp-content\/uploads\/sites\/9\/2026\/03\/1.37-replace-e1747983235343-768x321.png 768w, https:\/\/libraryresources.nse.org.ng\/fundamentalsoffoundationengineering\/wp-content\/uploads\/sites\/9\/2026\/03\/1.37-replace-e1747983235343-65x27.png 65w, https:\/\/libraryresources.nse.org.ng\/fundamentalsoffoundationengineering\/wp-content\/uploads\/sites\/9\/2026\/03\/1.37-replace-e1747983235343-225x94.png 225w, https:\/\/libraryresources.nse.org.ng\/fundamentalsoffoundationengineering\/wp-content\/uploads\/sites\/9\/2026\/03\/1.37-replace-e1747983235343-350x146.png 350w\" sizes=\"(max-width: 1100px) 100vw, 1100px\" \/><\/a><figcaption id=\"caption-attachment-79\" class=\"wp-caption-text\">Figure 1.37. (a) Reduction factor of undrained shear strength obtained from vane shear tests for embankment stability analyses (after Bjerrum 1972); (b) Reduction factor curves as function of the time to failure and of the plasticity index (after Chandler 1988).<\/figcaption><\/figure>\n<p>The advantage of the vane shear over other <em>in situ<\/em> testing methods for determining the undrained shear strength (CPTu, Eq. 1.16) is that the interpretation of the former is generally not sensitive to uncertainties regarding the shape of the failure surface (or value of the cone factor <em>N<sub>kt<\/sub><\/em>). It is widely accepted that rotation of a four-blade vane into soft soil will result in a cylindrical failure surface, and this is reflected in Eq. 1.34. Therefore, it is quite common to use vane shear tests to obtain site-specific cone factor values, in other words to calibrate the interpretation of cone test results on vane shear tests. Finally, it must be noted that the undrained shear strength measured by means of vane shear tests is the undrained strength under simple shear conditions (see Kouretzis <em>et al.<\/em> 2017), which in not equal to the undrained shear strength measured during common triaxial compression tests, as the stress path to failure is different. The implications of this when it comes to stability calculations are discussed in Part 5.<\/p>\n","protected":false},"author":1,"menu_order":10,"template":"","meta":{"pb_show_title":"","pb_short_title":"1.9 The Vane Shear Test","pb_subtitle":"","pb_authors":[],"pb_section_license":""},"chapter-type":[],"contributor":[],"license":[],"class_list":["post-82","chapter","type-chapter","status-publish","hentry"],"part":24,"_links":{"self":[{"href":"https:\/\/libraryresources.nse.org.ng\/fundamentalsoffoundationengineering\/wp-json\/pressbooks\/v2\/chapters\/82","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/libraryresources.nse.org.ng\/fundamentalsoffoundationengineering\/wp-json\/pressbooks\/v2\/chapters"}],"about":[{"href":"https:\/\/libraryresources.nse.org.ng\/fundamentalsoffoundationengineering\/wp-json\/wp\/v2\/types\/chapter"}],"author":[{"embeddable":true,"href":"https:\/\/libraryresources.nse.org.ng\/fundamentalsoffoundationengineering\/wp-json\/wp\/v2\/users\/1"}],"version-history":[{"count":1,"href":"https:\/\/libraryresources.nse.org.ng\/fundamentalsoffoundationengineering\/wp-json\/pressbooks\/v2\/chapters\/82\/revisions"}],"predecessor-version":[{"id":83,"href":"https:\/\/libraryresources.nse.org.ng\/fundamentalsoffoundationengineering\/wp-json\/pressbooks\/v2\/chapters\/82\/revisions\/83"}],"part":[{"href":"https:\/\/libraryresources.nse.org.ng\/fundamentalsoffoundationengineering\/wp-json\/pressbooks\/v2\/parts\/24"}],"metadata":[{"href":"https:\/\/libraryresources.nse.org.ng\/fundamentalsoffoundationengineering\/wp-json\/pressbooks\/v2\/chapters\/82\/metadata\/"}],"wp:attachment":[{"href":"https:\/\/libraryresources.nse.org.ng\/fundamentalsoffoundationengineering\/wp-json\/wp\/v2\/media?parent=82"}],"wp:term":[{"taxonomy":"chapter-type","embeddable":true,"href":"https:\/\/libraryresources.nse.org.ng\/fundamentalsoffoundationengineering\/wp-json\/pressbooks\/v2\/chapter-type?post=82"},{"taxonomy":"contributor","embeddable":true,"href":"https:\/\/libraryresources.nse.org.ng\/fundamentalsoffoundationengineering\/wp-json\/wp\/v2\/contributor?post=82"},{"taxonomy":"license","embeddable":true,"href":"https:\/\/libraryresources.nse.org.ng\/fundamentalsoffoundationengineering\/wp-json\/wp\/v2\/license?post=82"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}